For
testing the loop impedance function of the tester you simply
need a designated socket that is not protected by an
RCD. The reason for this is because some loop testers have the facility
to lock RCD's while carrying out their test. In this mode some
testers are not as accurate.
This is because maximum Zs of RCD
protected circuits is lower than circuits
without RCD protection. Some manufacturers have considered this
when designing their tester. I therefore recommend carrying out
impedance tests with the 'D-Loc' function disabled so
variations can easily be detected, and to do this you need a
non-RCD socket.
It is important to place a warning label
next to the socket, to explain that it is not protected by an
RCD, and that it is only to be used for meter accuracy checks.
The reason for this is because regulation 411.3.3 of
BS7671:2008 requires the label to be present.